1P/1P or 3P/1P Low Frequency Online UPS 6-10KVA

This transformer online UPS 6–10kVA provides reliable double-conversion power protection for servers, network equipment, telecom systems, industrial control devices, medical IT equipment, financial systems, security systems, and other critical single-phase loads. With galvanic isolation design, pure sine wave output, output power factor 0.8, wide input voltage and frequency range, and zero transfer time, it helps protect sensitive equipment from outages, voltage fluctuations, surges, and power quality problems.

Available in both 1-phase input / 1-phase output and 3-phase input / 1-phase output configurations, this UPS is suitable for different power supply environments. It features fully coated PCBAs, effective ventilation design, high short-circuit and overload capability, built-in maintenance bypass switch, LCD status display, RS-232/USB communication, dry contact signals, and optional SNMP monitoring. Standard battery and long-run external battery configurations are available to meet different backup time requirements.

Configuration Options

1P/1P Configuration

The 1-phase input / 1-phase output configuration is suitable for sites where both the mains power supply and protected equipment use single-phase power. It is commonly used in small server rooms, office IT systems, network rooms, telecom equipment, and commercial power protection applications.

3P/1P Configuration

The 3-phase input / 1-phase output configuration is suitable for facilities with 3-phase utility power but critical single-phase loads. It is commonly used in industrial facilities, commercial buildings, technical rooms, telecom rooms, and sites where 3-phase input power needs to support stable single-phase output equipment.

Features

Online Double-Conversion Technology

Online double-conversion technology provides continuous power conditioning and stable output power for sensitive and critical equipment.

Galvanic Isolation Design

Galvanic isolation helps provide electrical separation between input and output, improving protection for sensitive loads and demanding power environments.

1P/1P and 3P/1P Options

The UPS is available in both single-phase input / single-phase output and 3-phase input / single-phase output configurations to match different site power conditions.

Output Power Factor 0.8

Output power factor 0.8 provides practical active power capacity for IT, telecom, industrial, commercial, and critical electronic loads.

Pure Sine Wave Output

Pure sine wave output provides clean and stable power for servers, network equipment, communication devices, industrial controllers, and sensitive electronics.

Zero Transfer Time

Online double-conversion operation provides zero transfer time during mains power disturbances, helping maintain uninterrupted output power.

Wide Input Voltage Range

The wide input voltage range helps the UPS operate reliably in unstable mains power environments and reduces unnecessary battery discharge.

Wide Frequency Range

The UPS supports a wide input frequency range, improving adaptability in areas with unstable utility power or generator power.

High Short-Circuit and Overload Capability

High short-circuit and overload capability helps improve system robustness and supports demanding load conditions.

Fully Coated PCBAs

Fully coated PCBAs help improve resistance to harsh operating environments and support long-term reliability.

Effective Ventilation Design

The ventilation design supports heat dissipation and stable operation during continuous use.

Built-In Maintenance Bypass Switch

The built-in maintenance bypass switch allows easier service and maintenance while helping maintain power continuity when properly configured.

Standard and Long-Run Battery Options

Standard battery models provide built-in backup power, while long-run models support external battery configurations for extended runtime.

LCD Status Display

The LCD display provides UPS status, load level, battery level, input/output voltage and frequency, fault code, and warning code information.

RS-232 / USB Communication

Smart RS-232 and USB communication support UPS monitoring and power management with compatible systems.

Dry Contact Signals

Dry contact signals can provide status and alarm outputs, including AC failure, low battery, UPS alarm, bypass status, and UPS fault.

Optional SNMP Monitoring

Optional SNMP enables network-based UPS monitoring and power management through SNMP manager or web browser.

Specifications

MODELC-6K(L)C-7.5K(L)C-10K(L)
PHASESingle phase with ground
CAPACITY*6KVA/4.8KW7.5KVA/6KW10KVA/8KW
INPUT
Nominal Voltage208VAC/220VAC/230VAC
Voltage Range165VAC ~ 285VAC @ 16 pcs of batteries ; 185VAC ~ 285VAC @ 18 pcs of batteries
Frequency40 Hz ~ 55 Hz @ 50Hz system ; 56 Hz ~ 64 Hz @ 60Hz system
OUTPUT
Output Voltage208VAC/220VAC/230VAC
Voltage Regulation± 1%
Frequency Range (Synchronized Range)45Hz ~ 55 Hz or 56 Hz ~ 64 Hz
Frequency Range (Batt. Mode)50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Current Crest Ratio3:1
Harmonic Distortion≦ 3 % THD (Linear Load) ; ≦ 5 % THD (Non-linear Load)
Transfer TimeAC to DCZero
Inverter to BypassZero
Waveform (Batt. Mode)Pure Sinewave
EFFICIENCY
AC Mode88.3%
Battery Mode92%
BATTERY
Standard ModelBattery Type12V / 9Ah
Battery Numbers**16 pcs
Recharging Time6 hours recover to 90% capacity
Charging Current (max.)2A
Charging Voltage218.4 V ± 1%
Long-run ModelBattery TypeDepending on the applications
Numbers16 pcs18 pcs16 pcs18 pcs16 pcs18 pcs
Charging Current (max.)Default :8 A; 2A/4A/8A(Adjustable)
Charging Voltage218.4 V ± 1%245.7 V ± 1%218.4 V ± 1%245.7 V ± 1%218.4 V ± 1%245.7 V ± 1%
INDICATORS
LCDUPS status, load level, battery level, input/output voltage and frequency, fault code/warning code
ALARM
Battery ModeSounding every 4 seconds
Low BatterySounding every second
OverloadSounding twice every second
FaultContinously sounding
PHYSICAL
Standard ModelDimensions, DxWxH (mm)592 x 300 x 826
Net Weight (Kgs)106114122130130138
Long-run ModelDimensions, DxWxH (mm)592 x 250 x 826
Net Weight (Kgs)627886
ENVIRONMENT
Operating Temperature0 ~ 50°C (battery life cycle will be shorten when temperature is above 25°C)
Operating Humidity< 95 % and non-condensing
Noise LevelLess than 60dBA @ 1 Meter
MANAGEMENT
Smart RS-232/USBSupports Windows® Family, Linux and MAC
Dry ContactFive signals: AC failure, low battery, UPS alarm, bypass and UPS fault
Optional SNMPPower management from SNMP manager and web browser
* Derate capacity to 90% of capacity when the output voltage is adjusted to 208VAC.
**Battery number is set in factory and can’t be changed by users.
Product specifications are subject to change without further notice.

Specifications

MODEL3C-6K(L)3C-7.5K(L)3C-10K(L)
PHASE3-phase in / 1-phase out
CAPACITY*6KVA/4.8KW7.5KVA/6KW10KVA/8KW
INPUT
Nominal Voltage3 x 360VAC/380VAC/400VAC (3Ph + N + G)
Voltage Range286VAC ~ 493VAC @ 16 pcs of batteries ; 320VAC ~ 493VAC @ 18 pcs of batteries
Frequency40 Hz ~ 55 Hz @ 50Hz system ; 56 Hz ~ 64 Hz @ 60Hz system
OUTPUT
Output Voltage208VAC/220VAC/230VAC (Selectable)
Voltage Regulation± 1%
Frequency Range (Synchronized Range)45Hz ~ 55 Hz or 56 Hz ~ 64 Hz
Frequency Range (Batt. Mode)50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Current Crest Ratio3:1
Harmonic Distortion≦ 3 % THD (Linear Load) ; ≦ 5 % THD (Non-linear Load)
Transfer TimeAC to DCZero
Inverter to BypassZero
Waveform (Batt. Mode)Pure Sinewave
EFFICIENCY
AC Mode83%
Battery Mode92%
BATTERY
Standard ModelBattery Type12V / 9Ah
Battery Numbers**16 pcs
Recharging Time6 hours recover to 90% capacity
Charging Current (max.)2A
Charging Voltage218.4 V ± 1%
Long-run ModelBattery TypeDepending on the applications
Numbers16 pcs18 pcs16 pcs18 pcs16 pcs18 pcs
Charging Current (max.)Default :8 A; 2A/4A/8A(Adjustable)
Charging Voltage218.4 V ± 1%245.7 V ± 1%218.4 V ± 1%245.7 V ± 1%218.4 V ± 1%245.7 V ± 1%
INDICATORS
LCDUPS status, load level, battery level, input/output voltage and frequency, fault code/warning code
ALARM
Battery ModeSounding every 4 seconds
Low BatterySounding every second
OverloadSounding twice every second
FaultContinously sounding
PHYSICAL
Standard ModelDimensions, DxWxH (mm)592 x 300 x 826
Net Weight (Kgs)129137152160160168
Long-run ModelDimensions, DxWxH (mm)592 x 300 x 826
Net Weight (Kgs)84107115
ENVIRONMENT
Operating Temperature0 ~ 50°C (battery life cycle will be shorten when temperature is above 25°C)
Operating Humidity< 95 % and non-condensing
Noise LevelLess than 60dBA @ 1 Meter
MANAGEMENT
Smart RS-232/USBSupports Windows 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and MAC
Optional SNMPPower management from SNMP manager and web browser
* Derate capacity to 90% of capacity when the output voltage is adjusted to 208VAC.
**Battery number is set in factory and can’t be changed by users.
Product specifications are subject to change without further notice.

Applications

Server Rooms

Provides stable backup power for servers, storage systems, switches, firewalls, and small-to-medium IT infrastructure.

Network and Communication Rooms

Suitable for routers, switches, telecom equipment, communication systems, and network infrastructure requiring stable single-phase output power.

Telecom Equipment

Supports telecom systems, communication devices, edge network equipment, and transmission infrastructure.

Industrial Control Systems

Helps protect PLC systems, industrial PCs, monitoring equipment, automation devices, and control room infrastructure.

Medical IT Equipment

Suitable for healthcare IT rooms, medical workstations, diagnostic support systems, and selected sensitive medical electronics.

Financial and Banking Systems

Provides backup power for bank IT rooms, payment systems, branch infrastructure, security systems, and transaction-related equipment.

Security and Surveillance Systems

Supports CCTV systems, NVRs, access control devices, alarm systems, and security network equipment.

Commercial and Technical Facilities

Suitable for commercial buildings, equipment rooms, technical rooms, and infrastructure projects requiring stable single-phase output power.

Harsh Power Environments

Galvanic isolation, coated PCBAs, strong overload capability, and robust ventilation design make it suitable for sites with unstable grid power or demanding electrical conditions.

Frequently Asked Questions

What is this transformer online UPS used for?

This UPS is designed to provide backup power and power protection for servers, network equipment, telecom systems, medical IT equipment, industrial control devices, financial systems, security systems, and other critical single-phase loads.

What capacity range is available?

This UPS is available in 6kVA, 7.5kVA, and 10kVA, with output power ratings of 4.8kW, 6kW, and 8kW.

What is the difference between 1P/1P and 3P/1P?

1P/1P means single-phase input and single-phase output. It is suitable for sites with single-phase mains power.
3P/1P means 3-phase input and single-phase output. It is suitable for facilities with 3-phase mains power but single-phase critical equipment.

What is the benefit of galvanic isolation?

Galvanic isolation provides electrical separation between input and output, helping improve protection for sensitive equipment and reducing the impact of certain electrical disturbances.

Does this UPS provide pure sine wave output?

Yes. It provides pure sine wave output, making it suitable for servers, network equipment, telecom devices, industrial control systems, and sensitive electronics.

Does this UPS have zero transfer time?

Yes. As an online double-conversion UPS, it provides zero transfer time during mains power interruptions.

Does this UPS support long backup time?

Yes. Long-run models support external battery configurations, allowing backup time to be designed according to load and runtime requirements.

What communication options are available?

The UPS supports RS-232 and USB communication, dry contact signals, and optional SNMP monitoring.

Is this UPS suitable for harsh environments?

Yes. Fully coated PCBAs, effective ventilation design, galvanic isolation, and strong overload capability make it suitable for demanding power environments.

What information is needed to choose the right model?

To recommend the right model, the following information is usually required: load capacity, input voltage, output voltage, backup time, battery configuration, installation environment, communication requirements, and whether 1P/1P or 3P/1P configuration is required.