1P/1P Rack-Mount Online UPS 6KVA to 10KVA

This long-run rack-mount online UPS 1–3kVA provides reliable double-conversion power protection for applications requiring extended backup time. With external battery support, 4A maximum charging current, pure sine wave output, wide input voltage range, input power factor ≥0.99, output voltage regulation ±1%, and online zero-transfer operation, it is suitable for servers, network equipment, telecom systems, security systems, and critical small IT infrastructure.

The long-run design allows battery capacity to be configured according to the required runtime, making it a practical solution for unstable power areas, remote network sites, security systems, telecom rooms, and business applications that need longer backup power than standard internal battery models. LCD/LED display, RS-232 communication, and optional monitoring cards support convenient operation and remote management.

Features

Long-Run External Battery Design

The long-run model supports external battery connection, allowing backup time to be configured according to project requirements.

Online Double-Conversion Technology

Double-conversion online topology provides continuous power conditioning and stable output for sensitive equipment.

Compact Rack-Mount Chassis

The 2U rack-mounted design is suitable for server racks, network cabinets, telecom rooms, and security equipment cabinets.

Higher Charging Current

Long-run models support up to 4A charging current, helping recharge external battery systems more effectively.

Flexible Battery Voltage Design

External battery configurations are available for different models, supporting suitable DC voltage systems for 1kVA, 2kVA, and 3kVA units.

Pure Sine Wave Output

Pure sine wave output provides stable power for servers, network equipment, communication devices, and sensitive electronics.

Wide Input Voltage Range

The wide input voltage range of 90–300VAC helps the UPS operate reliably in areas with unstable utility power.

High Input Power Factor

Input power factor ≥0.99 supports efficient operation and helps reduce impact on upstream power systems.

Precise Output Voltage Regulation

Output voltage regulation of ±1% helps provide stable output power for critical equipment.

Zero Transfer Online Operation

Online operation provides continuous power protection without transfer interruption during power disturbances.

LCD and LED Display

Display options provide UPS status information such as operation mode, load level, battery level, input voltage, frequency, and system health status.

Optional Monitoring Cards

Optional NMC, MODBUS-485, USB, and dry contact cards support remote monitoring, alarm integration, and power management.

Suitable for Extended Runtime Applications

External battery support makes this UPS suitable for applications requiring longer backup time than standard internal battery models.

Specifications

MODELC6KRC6KRLC10KRC10KRL
CAPACITY6KVA/5.4KW10KVA/9KW
TOPOLOGYDouble Conversion Online UPS
PHASESingle Phase Input Single Phase Output
INPUT 
Input WiringL/N+PE
Nominal Voltage208/220/230/240VAC
Input Voltage RangeHV: 90~300VAC, LV: 55~145VAC
Frequency Range40Hz-70Hz
Input Power Factor≥0.99
OUTPUT 
Output WiringL/N+PE
Output VoltageHV: 208/220/230/240VAC, LV: 110/115/120/127VAC
Voltage Regulation±1%
Output Frequency50/60 ± 4Hz (Sync Mode) / 50/60 Hz ± 0.1% (Free Run)
Output WaveformPure Sine Wave
Output Distortion (THDV%)<2%(Linear Load), <7%(None-Linear Load)
Over Load Capability10Min@105%~125%, 1Min@125%~150%, 0.5Sec.@>150%
EFFICIENCY 
AC Mode91%93%
Battery Mode90%90%
BATTERY & CHARGER 
Battery Voltage144VDC144/192VDC192VDC192/240VDC
Battery Capacity12V/7Ah x 12pcsExternal12V/7Ah x 16pcsExternal
Backup Time≥6mins @ Half Load, ≥3mins @ Full Load (Standard)
Charging Current (max.)1A4A1A4A
PHYSICAL 
Chassis StyleRack-Mounted
Rack  Dimension438mm(W) x 88mm(2U)(H) x 500mm(D) without Battery
Battery Pack: 438mm(W) x 132mm(2U)(H) x 500mm(D)
Weight (kg)3715.44816
HMI 
LED DisplayMains / Battery Status, Load Level, Battery Level, Operation Mode
LCD DisplayInput Mains Voltage, Frequency, Load level, Operation Mode, Health Status
Standards CommunicationRS232 port
Optional Extension CardNMC Card, MODBUS-485 Card, USB Card, Dry Contact Card
ENVIRONMENT 
Temperature range0~40℃
Relative Humidity0-98% (Non-condensing)
Noise Level<50dB @ 1 meters
* Product specifications are subject to change without further notice.

Applications

Server Rooms

Provides extended backup power for servers, switches, storage devices, and small IT systems.

Network Cabinets

Suitable for routers, switches, firewalls, and communication equipment requiring longer backup time.

Telecom Rooms

Supports telecom devices, communication systems, and remote network equipment in unstable power environments.

Security and Surveillance Systems

Provides long backup support for CCTV systems, NVRs, access control devices, and security network equipment.

Remote IT Sites

Suitable for remote network cabinets, edge IT systems, and branch infrastructure where power interruptions may last longer.

Business-Critical Equipment

Protects office servers, VoIP systems, payment systems, communication devices, and critical small business equipment.

Industrial and Control Equipment

Can be used for selected control systems, industrial PCs, monitoring devices, and communication equipment requiring stable single-phase power.

Frequently Asked Questions

What is a long-run rack-mount online UPS?

A long-run rack-mount online UPS is an online UPS designed to connect with external batteries for longer backup time. It is suitable for applications where standard internal battery runtime is not enough.

What capacity range is available?

The long-run models are available in 1kVA, 2kVA, and 3kVA capacities, with output power ratings of 800W, 1.6kW, and 2.4kW.

Does the long-run model include internal batteries?

No. The long-run models are designed for external battery connection. Battery capacity can be selected according to the required backup time and project design.

What is the charging current of the long-run model?

The long-run models support up to 4A maximum charging current, which is suitable for external battery configurations.

What is the difference between the standard model and long-run model?

The standard model includes internal batteries for short-term backup. The long-run model uses external batteries and is designed for longer backup time.

Is this UPS suitable for telecom and security systems?

Yes. It is suitable for telecom equipment, network cabinets, security systems, NVRs, access control devices, and communication equipment requiring extended backup power.

Does this UPS provide pure sine wave output?

Yes. It provides pure sine wave output for sensitive IT, telecom, and electronic equipment.

What monitoring options are available?

Standard RS-232 communication is available, with optional NMC, MODBUS-485, USB, and dry contact cards for monitoring and integration.

What information is needed to configure backup time?

To configure backup time, provide the load capacity, required runtime, battery voltage, battery capacity, available installation space, and whether battery cabinets or external battery packs are required.

What information is needed to choose the right model?

To choose the right model, provide the equipment list, total load, input/output voltage, required backup time, rack installation conditions, monitoring needs, and external battery requirements.