Features
True Online Double-Conversion
True online double-conversion technology provides continuous power protection and helps isolate connected equipment from mains power disturbances.
DSP Technology
DSP control improves system reliability, response accuracy, and power management performance for critical applications.
Output Power Factor 1.0
Output power factor 1.0 delivers more usable active power, helping support modern servers, network equipment, and sensitive electronic loads.
Rack/Tower Convertible Design
The standard 19-inch form factor supports both rack-mounted and tower installation, providing greater flexibility for server rooms, network cabinets, and equipment rooms.
Hot-Swappable Modular Connector Box
The modular connector box design allows easier power expansion, installation, and maintenance. Power modules can be removed from the cabinet without disconnecting wires, helping reduce service complexity.
Parallel Operation Support
Multiple UPS units can operate in parallel to increase system capacity or improve redundancy, making the UPS suitable for scalable power protection projects.
Common Battery Support
Parallel systems can share common battery packs, helping reduce system cost and simplify battery configuration while maintaining backup performance.
Adjustable Battery Design
Battery quantity can be adjusted according to different power demands and backup time requirements, offering greater flexibility for project configuration.
50Hz/60Hz Frequency Converter Mode
Frequency converter mode allows the output frequency to be locked at 50Hz or 60Hz, supporting power-sensitive equipment and special application requirements.
ECO Mode for Energy Saving
ECO mode improves operating efficiency and helps reduce energy consumption when power conditions are suitable.
Emergency Power Off Function
The EPO function allows the UPS system to be shut down quickly in emergency situations when connected to the proper control mechanism.
Generator Compatible
Generator compatibility allows the UPS to accept generator power and continue supplying stable output power to connected loads.
LCD/LED Status Display
The display provides UPS status information such as load level, battery level, input/output voltage, discharge time, and fault conditions.
Optional SNMP Monitoring
Optional SNMP support enables network-based monitoring and power management through SNMP manager or web browser.
Specifications
| MODEL | 3/3-10K | 3/1-10K | 1/1-10K | |
| PHASE | 3 phase in / 3 phase out | 3 phase in / 1 phase out | 1 phase in / 1 phase out | |
| CAPACITY | 10000 VA / 10000 W | 10000 VA / 10000 W | 10000 VA / 10000 W | |
| PARALLEL CAPABILITY | 10 | 10 | 10 | |
| INPUT | ||||
| Nominal Voltage | 3 x 360VAC/380VAC/ 400VAC/415VAC (3Ph+N+PE) | 3 x 360VAC/380VAC/ 400VAC/415VAC (3Ph+N+PE) | 208VAC/220VAC/230VAC /240VAC (1Ph+N+PE) | |
| Voltage Range | 190-520 VAC (3-phase) @ 50% load 305-478 VAC (3-phase) @ 100% load | 110-300 VAC @ 50% load 176-276 VAC @ 100% load | ||
| Frequency Range | 40 Hz ~ 70 Hz | |||
| Power Factor | ≧ 0.99 @ 100% load | |||
| THDi | < 4% @ full linear load | |||
| OUTPUT | ||||
| Output Voltage | 360VAC/380VAC/400VAC/ 415VAC (3Ph+N) | 208*/220/230/240VAC (L+N) | 208*/220/230/240VAC (L+N) | |
| AC Voltage Regulation (Batt. Mode) | ± 1% | |||
| Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz | |||
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | |||
| Current Crest Ratio | 3:1 (max.) | |||
| Harmonic Distortion | ≦ 2% THD (Linear Load) ; ≦ 3% THD (Non-linear Load) | |||
| Transfer Time | AC Mode to Batt. Mode | Zero | ||
| Inverter to Bypass | Zero | |||
| Waveform (Batt. Mode) | Pure Sinewave | |||
| EFFICIENCY | ||||
| AC Mode | 94% | 94% | 93.5% | |
| ECO Mode | 97% | 97% | 97% | |
| Battery Mode | At Full Load | 93% | 92.5% | 92% |
| Peak | 93.5% | 93% | 92.5% | |
| BATTERY CHARGER | ||||
| Battery Voltage | ± 12V / 9 Ah | |||
| Battery Numbers | 16 ~ 20 pcs (adjustable) x 2 | 16 ~ 20 pcs (adjustable) x 2 | 16 ~ 20 pcs (adjustable) x 2 | |
| Nominal Voltage | +/-192V (12V x 32 pcs) | +/-192V (12V x 32 pcs) | +/-192V (12V x 32 pcs) | |
| Maximum Voltage | +/- 240V (12V x 40 pcs) | +/- 240V (12V x 40 pcs) | +/- 240V (12V x 40 pcs) | |
| Minimum Voltage | +/-192V (12V x 32 pcs) | +/-192V (12V x 32 pcs) | +/-192V (12V x 32 pcs) | |
| Charging Voltage | ± 218V | ± 218V | ± 218V | |
| Typical Recharging Time | 9 hours recover to 90% capacity | |||
| Charging Current | ± 4A | |||
| INDICATORS | ||||
| LCD/LED Display | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | |||
| PHYSICAL | ||||
| Dimension, D x W x H(mm) | 678 x 418 x 129 [3U] | |||
| Net Weight (kgs) | 20.5 | 20.5 | 20.5 | |
| ENVIRONMENT | ||||
| Operating Humidity | 0-95 % RH @ 0- 40°C (non-condensing) | |||
| Noise Level | Less than 55dB @ 1 Meter | Less than 55dB @ 1 Meter | Less than 55dB @ 1 Meter | |
| MANAGEMENT | ||||
| Smart RS-232/USB | Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux and MAC | |||
| Optional SNMP | Power management from SNMP manager and web browser | |||
| *Derate capacity to 90% of capacity when the output voltage is adjusted to 208VAC. | ||||
| Product specifications are subject to change without further notice | ||||
Applications
Server Rooms
Provides stable backup power for servers, storage systems, switches, firewalls, and critical IT equipment.
Network Rooms
Suitable for routers, switches, communication equipment, and network infrastructure requiring reliable online power protection.
Telecom Systems
Supports telecom equipment, communication systems, and network devices that require clean and continuous power.
Industrial Control Systems
Helps protect PLC systems, industrial PCs, monitoring equipment, and control room devices from power interruptions and voltage disturbances.
Medical IT Equipment
Suitable for healthcare IT rooms, medical workstations, monitoring systems, and selected diagnostic support equipment.
Financial and Banking Systems
Provides backup power for bank IT rooms, payment systems, branch infrastructure, security systems, and transaction-related equipment.
Commercial Office IT Infrastructure
Supports office servers, network cabinets, VoIP systems, security devices, and business-critical electronics.
Security and Surveillance Systems
Helps maintain power for CCTV, NVR systems, access control devices, alarm systems, and security network equipment.
Education and Research Facilities
Suitable for computer labs, campus IT systems, laboratory equipment, and research data systems.
Frequently Asked Questions
What is this rack/tower online UPS used for?
This UPS is designed to provide reliable online power protection for servers, network equipment, telecom systems, industrial control devices, medical IT systems, financial equipment, security systems, and other critical loads.
What does rack/tower convertible design mean?
Rack/tower convertible design means the UPS can be installed either in a standard 19-inch rack or used as a tower unit. This provides flexibility for server rooms, network cabinets, offices, and equipment rooms.
What is the benefit of true online double-conversion technology?
True online double-conversion technology provides continuous power conditioning and stable output power, helping protect connected equipment from outages, voltage fluctuations, frequency instability, surges, and other power disturbances.
Does this UPS support parallel operation?
Yes. Multiple units can be connected in parallel to increase system capacity or improve redundancy, depending on the project design.
Can this UPS use a common battery system?
Yes. In parallel operation, multiple UPS units can share common battery packs, helping reduce battery system cost and simplify configuration while maintaining backup performance.
What is the advantage of output power factor 1.0?
Output power factor 1.0 means the UPS can deliver more usable active power. This helps improve capacity utilization and better supports modern IT and critical electronic equipment.
Does this UPS support generator power?
Yes. The UPS is generator compatible and can work with generator input in suitable backup power systems, helping provide stable power to connected loads.
What is ECO mode?
ECO mode is an energy-saving operating mode that helps improve efficiency when input power conditions are stable and suitable.
What is EPO function?
EPO stands for Emergency Power Off. It allows the UPS to be shut down quickly in emergency situations when connected to the proper external control system.
What information is needed to choose the right UPS configuration?
To recommend the right configuration, the following information is usually required: load capacity, input/output voltage, phase requirement, backup time, installation method, battery configuration, parallel requirement, generator status, monitoring needs, and future expansion plan.