3P/1P High Frequency Online UPS 10KVA

This 3P/1P online UPS 10kVA provides reliable double-conversion power protection for servers, network equipment, telecom devices, security systems, medical IT equipment, and small critical power applications. With 3-phase input and single-phase output, pure sine wave output, DSP control, output power factor 0.8, active power factor correction, and zero transfer time, it helps protect sensitive equipment from outages, voltage fluctuations, surges, and power quality problems.

The 10kVA model supports wide input voltage range, 50Hz/60Hz frequency converter mode, ECO mode, programmable power management outlets, EPO function, generator compatibility, LCD status display, SNMP/USB/RS-232 communication, adjustable battery numbers, and standard or long-run battery configurations. It is suitable for small server rooms, network rooms, telecom cabinets, office IT systems, and light commercial backup power applications.

Features

True Online Double-Conversion

Provides continuous power conditioning and stable output power for sensitive and critical equipment.

3-Phase Input / Single-Phase Output

Uses 3-phase input and single-phase output, making it suitable for facilities with 3-phase mains power and critical single-phase loads.

10kVA / 8kW Capacity

The 10kVA model provides 8kW active power, suitable for small server rooms, network equipment, telecom devices, and office IT infrastructure.

DSP Control Technology

DSP control improves system performance, response accuracy, and operating reliability.

Output Power Factor 0.8

Output power factor 0.8 provides practical power capacity for IT, telecom, and commercial power protection applications.

Active Power Factor Correction

Active power factor correction helps improve input power quality and reduce impact on upstream electrical systems.

Pure Sine Wave Output

Pure sine wave output provides clean and stable power for servers, network equipment, communication devices, and sensitive electronics.

Zero Transfer Time

Online double-conversion operation provides zero transfer time during mains power disturbances.

ECO Mode for Energy Saving

ECO mode helps improve operating efficiency and reduce energy consumption when input power conditions are stable.

Frequency Converter Mode

Supports 50Hz/60Hz frequency converter mode for equipment requiring fixed output frequency.

Generator Compatible

Can work with generator input in suitable backup power environments.

Programmable Power Management Outlets

Programmable outlets allow selected loads to be managed based on backup priority.

Emergency Power Off Function

EPO allows fast UPS shutdown in emergency situations when properly connected.

Flexible Battery Configuration

Adjustable battery numbers and long-run battery options support different backup time requirements.

Multiple Communication Interfaces

SNMP, USB, and RS-232 communication support local monitoring, remote management, and power management integration.

LCD Status Display

LCD display shows UPS status, load level, battery level, input/output voltage, discharge time, and fault information.

Specifications

MODEL3/1-10K (L)
PHASE3-phase in / 1-phase out
CAPACITY10000 VA  / 8000 W
INPUT
Nominal Voltage3 x 400 VAC (3Ph+N)
Voltage Range190-520 VAC (3-phase) @ 50% load ; 305-478 VAC (3-phase) @ 100% load
Frequency Range46~54Hz or 56~64Hz
Power Factor≧ 0.99 @ 100% Load
THDi< 6% @ 100% load
OUTPUT
Output Voltage208/220/230/240VAC
AC Voltage Regulation (Batt. Mode)± 1%
Frequency Range (Synchronized Range)46~54Hz or 56~64Hz
Frequency Range (Batt. Mode)50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio3:1 (max.)
Harmonic Distortion≦ 2 % THD (Line ar Load); ≦ 5 % THD (Non-linear Load)
Transfer TimeAC Mode to Batt. ModeZero
Inverter to BypassZero
Waveform (Batt. Mode)Pure Sinewave
EFFICIENCY
AC Mode91.5%
ECO Mode97%
Battery Mode87%
BATTERY
Standard ModelBattery Type12 V / 9 Ah
Numbers20 pcs (18 – 20 pcs adjustable)*
Typical Recharge Time9 hours recover to 90% capacity
Charging Current (max.)1A
Charging Voltage273 VDC ± 1% (Based on 20pcs batteries)
Long-run ModelBattery TypeDepending on applications
Numbers
Charging Current (max.)4A
Charging Voltage273 VDC ± 1%  (Based on 20pcs batteries)
INDICATORS
LCD DisplayUPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
ALARM
Battery ModeSounding every 4 seconds
Low BatterySounding every second
OverloadSounding twice every second
FaultContinously sounding
PHYSICAL
Standard ModelDimension, D x W x H (mm)592 x 250 x 576
Net Weight (kgs)83
Long-run ModelDimension, D x W x H (mm)592 x 250 x 576
Net Weight (kgs)28
ENVIRONMENT
Operating Humidity0-95 % RH @ 0- 40°C (Non-condensing)
Noise LevelLess than 58dB @ 1 Meter
MANAGEMENT
Smart RS-232 / USBSupports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux and MAC
Optional SNMPPower management from SNMP manager and web browser
* L means long-run model.
**When using internal batteries from 18-19, the unit will de-rate according to below formula: P = PRating x N/20.
**Derate capacity to 90% of capacity when the output voltage is adjusted to 208VAC.
Product specifications are subject to change without further notice.

Applications

Small Server Rooms

Provides reliable backup power for servers, storage systems, switches, and firewalls.

Network Rooms

Protects routers, switches, telecom devices, and communication equipment.

Office IT Infrastructure

Suitable for office servers, NAS systems, VoIP systems, and business-critical electronics.

Security Systems

Supports CCTV systems, NVRs, access control devices, and alarm systems.

Telecom Equipment

Protects small telecom cabinets, communication devices, and edge network equipment.

Medical IT Equipment

Suitable for medical workstations, healthcare IT systems, and selected sensitive medical electronics.

Retail and POS Systems

Provides backup power for POS terminals, payment devices, store networks, and security equipment.

Frequently Asked Questions

What is this 10kVA 3P/1P online UPS used for?

It is used to protect servers, network equipment, telecom devices, security systems, office IT equipment, and other critical single-phase loads.

What does 3P/1P mean?

3P/1P means 3-phase input and single-phase output. It is suitable for sites with 3-phase mains power but single-phase protected equipment.

What is the output power of the 10kVA model?

The 10kVA model provides 8kW of active power.

Does this UPS provide pure sine wave output?

Yes. It provides pure sine wave output for sensitive IT, telecom, and electronic equipment.

Does this UPS have zero transfer time?

Yes. As an online double-conversion UPS, it provides zero transfer time during mains power interruptions.

Can this UPS work with a generator?

Yes. It is generator compatible and can work with generator input in suitable backup power systems.

Does this UPS support remote monitoring?

Yes. It supports SNMP, USB, and RS-232 communication for monitoring and power management.

Is this UPS suitable for long backup time?

Yes. Long-run battery configurations can be used according to required backup time.