Features
True Online Double-Conversion
Provides continuous power conditioning and stable output power for sensitive and critical equipment.
3-Phase Input / Single-Phase Output
Uses 3-phase input and single-phase output, making it suitable for facilities with 3-phase mains power and critical single-phase loads.
10kVA / 8kW Capacity
The 10kVA model provides 8kW active power, suitable for small server rooms, network equipment, telecom devices, and office IT infrastructure.
DSP Control Technology
DSP control improves system performance, response accuracy, and operating reliability.
Output Power Factor 0.8
Output power factor 0.8 provides practical power capacity for IT, telecom, and commercial power protection applications.
Active Power Factor Correction
Active power factor correction helps improve input power quality and reduce impact on upstream electrical systems.
Pure Sine Wave Output
Pure sine wave output provides clean and stable power for servers, network equipment, communication devices, and sensitive electronics.
Zero Transfer Time
Online double-conversion operation provides zero transfer time during mains power disturbances.
ECO Mode for Energy Saving
ECO mode helps improve operating efficiency and reduce energy consumption when input power conditions are stable.
Frequency Converter Mode
Supports 50Hz/60Hz frequency converter mode for equipment requiring fixed output frequency.
Generator Compatible
Can work with generator input in suitable backup power environments.
Programmable Power Management Outlets
Programmable outlets allow selected loads to be managed based on backup priority.
Emergency Power Off Function
EPO allows fast UPS shutdown in emergency situations when properly connected.
Flexible Battery Configuration
Adjustable battery numbers and long-run battery options support different backup time requirements.
Multiple Communication Interfaces
SNMP, USB, and RS-232 communication support local monitoring, remote management, and power management integration.
LCD Status Display
LCD display shows UPS status, load level, battery level, input/output voltage, discharge time, and fault information.
Specifications
| MODEL | 3/1-10K (L) | |
| PHASE | 3-phase in / 1-phase out | |
| CAPACITY | 10000 VA / 8000 W | |
| INPUT | ||
| Nominal Voltage | 3 x 400 VAC (3Ph+N) | |
| Voltage Range | 190-520 VAC (3-phase) @ 50% load ; 305-478 VAC (3-phase) @ 100% load | |
| Frequency Range | 46~54Hz or 56~64Hz | |
| Power Factor | ≧ 0.99 @ 100% Load | |
| THDi | < 6% @ 100% load | |
| OUTPUT | ||
| Output Voltage | 208/220/230/240VAC | |
| AC Voltage Regulation (Batt. Mode) | ± 1% | |
| Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz | |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | |
| Current Crest Ratio | 3:1 (max.) | |
| Harmonic Distortion | ≦ 2 % THD (Line ar Load); ≦ 5 % THD (Non-linear Load) | |
| Transfer Time | AC Mode to Batt. Mode | Zero |
| Inverter to Bypass | Zero | |
| Waveform (Batt. Mode) | Pure Sinewave | |
| EFFICIENCY | ||
| AC Mode | 91.5% | |
| ECO Mode | 97% | |
| Battery Mode | 87% | |
| BATTERY | ||
| Standard Model | Battery Type | 12 V / 9 Ah |
| Numbers | 20 pcs (18 – 20 pcs adjustable)* | |
| Typical Recharge Time | 9 hours recover to 90% capacity | |
| Charging Current (max.) | 1A | |
| Charging Voltage | 273 VDC ± 1% (Based on 20pcs batteries) | |
| Long-run Model | Battery Type | Depending on applications |
| Numbers | ||
| Charging Current (max.) | 4A | |
| Charging Voltage | 273 VDC ± 1% (Based on 20pcs batteries) | |
| INDICATORS | ||
| LCD Display | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | |
| ALARM | ||
| Battery Mode | Sounding every 4 seconds | |
| Low Battery | Sounding every second | |
| Overload | Sounding twice every second | |
| Fault | Continously sounding | |
| PHYSICAL | ||
| Standard Model | Dimension, D x W x H (mm) | 592 x 250 x 576 |
| Net Weight (kgs) | 83 | |
| Long-run Model | Dimension, D x W x H (mm) | 592 x 250 x 576 |
| Net Weight (kgs) | 28 | |
| ENVIRONMENT | ||
| Operating Humidity | 0-95 % RH @ 0- 40°C (Non-condensing) | |
| Noise Level | Less than 58dB @ 1 Meter | |
| MANAGEMENT | ||
| Smart RS-232 / USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux and MAC | |
| Optional SNMP | Power management from SNMP manager and web browser | |
| * L means long-run model. | ||
| **When using internal batteries from 18-19, the unit will de-rate according to below formula: P = PRating x N/20. | ||
| **Derate capacity to 90% of capacity when the output voltage is adjusted to 208VAC. | ||
| Product specifications are subject to change without further notice. | ||
Applications
Small Server Rooms
Provides reliable backup power for servers, storage systems, switches, and firewalls.
Network Rooms
Protects routers, switches, telecom devices, and communication equipment.
Office IT Infrastructure
Suitable for office servers, NAS systems, VoIP systems, and business-critical electronics.
Security Systems
Supports CCTV systems, NVRs, access control devices, and alarm systems.
Telecom Equipment
Protects small telecom cabinets, communication devices, and edge network equipment.
Medical IT Equipment
Suitable for medical workstations, healthcare IT systems, and selected sensitive medical electronics.
Retail and POS Systems
Provides backup power for POS terminals, payment devices, store networks, and security equipment.
Frequently Asked Questions
What is this 10kVA 3P/1P online UPS used for?
It is used to protect servers, network equipment, telecom devices, security systems, office IT equipment, and other critical single-phase loads.
What does 3P/1P mean?
3P/1P means 3-phase input and single-phase output. It is suitable for sites with 3-phase mains power but single-phase protected equipment.
What is the output power of the 10kVA model?
The 10kVA model provides 8kW of active power.
Does this UPS provide pure sine wave output?
Yes. It provides pure sine wave output for sensitive IT, telecom, and electronic equipment.
Does this UPS have zero transfer time?
Yes. As an online double-conversion UPS, it provides zero transfer time during mains power interruptions.
Can this UPS work with a generator?
Yes. It is generator compatible and can work with generator input in suitable backup power systems.
Does this UPS support remote monitoring?
Yes. It supports SNMP, USB, and RS-232 communication for monitoring and power management.
Is this UPS suitable for long backup time?
Yes. Long-run battery configurations can be used according to required backup time.